DE-GermanPL-Polish

SIPOS 5 Flash basics


Two electronics variants

ECOTRON - PROFITRON

ECOTRON

Especially suitable for standard actuators and simple modulating control functions with control via OPEN, CLOSE and STOP commands.
Feedback to DCS:
5 programmable signal outputs. An analog 4-20 mA feedback signal  or fieldbus interface is available as an option.

The ECOTRON is set by means of DIP switches and potentiometers. LEDs indicate the current operating status and are also used for indicating faults and facilitating diagnosis.

PROFITRON

Ideally suited to the high-tech modulating actuator applications, but also applicable to more standard installations.
In addition to control by means of switching commands, the PROFITRON has an input for emergency operation and an
2 optional 0/4-20 mA inputs for the integrated positioner and additional software functions. Fieldbus interfaces are also available.

Feedback to DCS:
8 freely programmable signal outputs and a 0/4-20 mA feedback signal.

With plain-text display the PROFITRON electronics can be used to monitor, diagnose and, if necessary, enable actuator configuration.

The language of the display can be selected as required.


SIPOS 5 Flash
ECOTRONPROFITRON
Inputs and outputs
Control inputs OPEN, CLOSE, STOP (electrically isolated)
Control input EMERGENCY (electrically isolated)
24V external power supply possible
Setpoint 0/4...20 mA (optional electrically isolated)
Open-circuit detection
Pulse/permanent contact control
Control via threshold switch
Two-wire control
Control mode REMOTE switchable
Signaling outputs 24 V (electrically isolated)58
Relay outputs (each NC, NO)55
Position feedback signal 0/4...20 mA
(optional electrically isolated)
Fieldbus interface
PROFIBUS DP 1-channel (optional with fiber-optics)
or 2-channels
MODBUS RTU 1-channel (optional with fiber-optics)
or 2-channels
Communication with parameterization tools
DTM for FDT
EDD for PDM
COM-SIPOS
Adjustment / parameterization possibilities
Tripping torque OPEN/CLOSE
Output speed steps77
Independently adjustable output speeds
for OPEN, CLOSE, EMERGENCY OPEN/CLOSE
14
Cut-off mode (travel / torque dependent)
Direction of rotation
Retry when blocked in move
Intermediate contacts2
Motor protection bypass
Motor heater
Maintenance intervals
Software functions
Positioner (adaptive three-point controller)
Proportional / split-range function
Process controller
Travel-speed characteristic curve
Analog output speed setpoint
Travel-dependent freely adjustable positioning times
Miscellaneous
Local control station
(lockable with padlock/protective cap)
Multilingual display
LED display REMOTE / LOCAL
LED display OPEN / CLOSE / running indication
Soft start-up
Valve torque reference curve recording
(3 reference curves)
Diagnostic data
Motor temperature monitoring
Automatic phase sequence correction
Imprint   Privacy policy   Sitemap   Login   Contact address: General   Sales   Service